Veris CWV2 Wall Mount Air Quality Sensor

Model: CWV2

Veris CWV2 Wall Mount Air Quality Sensor

Model: CWV2

A wall mount, non-dispersive infrared (NDIR) sensor designed for measuring environmental CO2 concentration in indoor living spaces.

A wall mount, non-dispersive infrared (NDIR) sensor designed for measuring environmental CO2 concentration in indoor living spaces.

Sale Price $123.51 USD
Regular Price $501.44 USD
Availability 3 to 4 Weeks
Quantity

Veris CWV2 Offers

Designed for measuring CO2 levels in living spaces, the CWV2 is ideal for use with Building Automation Systems (BAS) controllers that accept 4 to 20mA, 0 to 5 VDC, or 0 to 10 VDC outputs. Measuring CO2 levels from 0 to 2000 ppm, this air quality sensor has an accuracy of ±40 ppm ±5.5% of the measured value and is ideal for bid-spec applications.

Features

  • Large wiring terminals on baseplate and snap-on covers with security screw simplify installation and service
  • Field-selectable outputs for operational flexibility
  • Unique self-calibration algorithm improves long-term stability and accuracy
  • Compliant with ASHRAE and other standards for ventilation control

Applications

  • Optimize demand-controlled ventilation by adjusting the amount of outdoor air introduced based on CO2 levels
  • Ensure that CO2 levels remain within safe limits within office spaces, promoting a healthier and more productive work environment
  • Maintain air quality in retail spaces to enhance customer comfort and reduce potential health risks
  • Help maintain appropriate CO2 levels to ensure a conducive learning environment in classrooms and lecture halls
  • Monitor air quality in hospitals and clinics to prevent the spread of airborne diseases and ensure a safe environment for patients and staff​
  • Use in smart home systems to maintain air quality, ensuring a healthy living environment for occupants​
  • Ensure guest comfort in hotels and restaurants by maintaining optimal indoor air quality
  • Monitor CO2 levels in manufacturing plants to ensure worker safety and compliance with industrial health regulations​
  • Help manage air quality in public buildings with fluctuating occupancy, enhancing visitor comfort and safety​
  • Ensure air quality in large, enclosed spaces with high foot traffic, such as airports and train stations, to prevent discomfort and health issues among travelers

Veris CWV2 Specifications

Sensor Type Dual-beam, non-dispersive infrared (NDIR), diffusion sampling
CO2 Output Range 0 to 2000 ppm
Accuracy ±40 ppm ±5.5% of measured value
Repeatability ±30 ppm ±4.5% of measured value
Response Time ≤75 seconds for 90° step change
Input Power Class 2; 20 to 30 Vdc, 24 Vac, 50 to 60 Hz
Max. Current 45 mA
Analog Output Selectable 4 to 20 mA, 0 to 5 V, 0 to 10 V
Operating Temperature 0 to 50°C (32 to 122°F)
Operating Humidity 0 to 95% RH non-condensing
Housing Material High-impact ABS plastic
Terminal Block Torque 0.5 to 0.6 N-m (0.37 to 0.44 in-lbf)
Click here for complete specifications on the Veris CWV2

What's included with the Veris CWV2

  • Veris CWV2 Wall Mount Air Quality Sensor

Veris CWV2 Offers

Designed for measuring CO2 levels in living spaces, the CWV2 is ideal for use with Building Automation Systems (BAS) controllers that accept 4 to 20mA, 0 to 5 VDC, or 0 to 10 VDC outputs. Measuring CO2 levels from 0 to 2000 ppm, this air quality sensor has an accuracy of ±40 ppm ±5.5% of the measured value and is ideal for bid-spec applications.

Features

  • Large wiring terminals on baseplate and snap-on covers with security screw simplify installation and service
  • Field-selectable outputs for operational flexibility
  • Unique self-calibration algorithm improves long-term stability and accuracy
  • Compliant with ASHRAE and other standards for ventilation control

Applications

  • Optimize demand-controlled ventilation by adjusting the amount of outdoor air introduced based on CO2 levels
  • Ensure that CO2 levels remain within safe limits within office spaces, promoting a healthier and more productive work environment
  • Maintain air quality in retail spaces to enhance customer comfort and reduce potential health risks
  • Help maintain appropriate CO2 levels to ensure a conducive learning environment in classrooms and lecture halls
  • Monitor air quality in hospitals and clinics to prevent the spread of airborne diseases and ensure a safe environment for patients and staff​
  • Use in smart home systems to maintain air quality, ensuring a healthy living environment for occupants​
  • Ensure guest comfort in hotels and restaurants by maintaining optimal indoor air quality
  • Monitor CO2 levels in manufacturing plants to ensure worker safety and compliance with industrial health regulations​
  • Help manage air quality in public buildings with fluctuating occupancy, enhancing visitor comfort and safety​
  • Ensure air quality in large, enclosed spaces with high foot traffic, such as airports and train stations, to prevent discomfort and health issues among travelers

Veris CWV2 Specifications

Sensor Type Dual-beam, non-dispersive infrared (NDIR), diffusion sampling
CO2 Output Range 0 to 2000 ppm
Accuracy ±40 ppm ±5.5% of measured value
Repeatability ±30 ppm ±4.5% of measured value
Response Time ≤75 seconds for 90° step change
Input Power Class 2; 20 to 30 Vdc, 24 Vac, 50 to 60 Hz
Max. Current 45 mA
Analog Output Selectable 4 to 20 mA, 0 to 5 V, 0 to 10 V
Operating Temperature 0 to 50°C (32 to 122°F)
Operating Humidity 0 to 95% RH non-condensing
Housing Material High-impact ABS plastic
Terminal Block Torque 0.5 to 0.6 N-m (0.37 to 0.44 in-lbf)
Click here for complete specifications on the Veris CWV2