Engineered for precise proportional control, this universal pneumatic receiver-controller supports single or dual inputs and remote set point adjustment. Ideal for regulating pneumatic actuated dampers and valves in HVAC/R systems, it enables accurate control of temperature, humidity, or pressure when used with remote transmitters. Includes protective cover.
Engineered for precise proportional control, this universal pneumatic receiver-controller supports single or dual inputs and remote set point adjustment. Ideal for regulating pneumatic actuated dampers and valves in HVAC/R systems, it enables accurate control of temperature, humidity, or pressure when used with remote transmitters. Includes protective cover.
Features
| Receiver-Controller | Forced balanced pneumatic amplifier. Relay type |
| Setpoint | Adjustable °F, °C, in. water mm water, % relative humidity labels (included with controller) |
| Input Signals | 3 to 15 psig (21 to 103 kPa) typically from a transmitter or remote setpoint. Maximum 30 psig (207 kPa) |
| Output Air Signal | From 0.5 psig (3.4 kPa) to within 0.5 psig (3.4 kPa) of supply air pressure |
| Supply Air Pressure | Nominal: 20 psig (138 kPa) Minimum: 18 psig (124 kPa) Maximum: 30 psig (207 kPa) Clean, oil free, dry air required |
| Air Connections | Field connections: Barb connectors for 1/4" O.D. plastic tubing or 1/8" FNPT by removing barb connectors Gauge ports: 1/8" FNPT for 1-1/2" diameter gauges such as AL-362 or AKS-6XXX series receiver gauges |
| Air Consumption for Sizing Air Compressors | 0.008 scfm (3.8 ml/s) plus 0.024 scfm (11.4 ml/s) for each transmitter and remote setpoint |
| Air Capacity for Sizing Air Mains | 16 scim (4.4 ml/s) plus 36 scim (13.2 ml/s) for each transmitter and remote setpoint |
| Mounting | Upright on surface of wall or panel |
| Dimensions | 6-3/4 x 7-7/16 x 4" (172 x 189 x 102 mm) |
| Receiver-Controller | Forced balanced pneumatic amplifier. Relay type |
| Setpoint | Adjustable °F, °C, in. water mm water, % relative humidity labels (included with controller) |
| Input Signals | 3 to 15 psig (21 to 103 kPa) typically from a transmitter or remote setpoint. Maximum 30 psig (207 kPa) |
| Output Air Signal | From 0.5 psig (3.4 kPa) to within 0.5 psig (3.4 kPa) of supply air pressure |
| Supply Air Pressure | Nominal: 20 psig (138 kPa) Minimum: 18 psig (124 kPa) Maximum: 30 psig (207 kPa) Clean, oil free, dry air required |
| Air Connections | Field connections: Barb connectors for 1/4" O.D. plastic tubing or 1/8" FNPT by removing barb connectors Gauge ports: 1/8" FNPT for 1-1/2" diameter gauges such as AL-362 or AKS-6XXX series receiver gauges |
| Air Consumption for Sizing Air Compressors | 0.008 scfm (3.8 ml/s) plus 0.024 scfm (11.4 ml/s) for each transmitter and remote setpoint |
| Air Capacity for Sizing Air Mains | 16 scim (4.4 ml/s) plus 36 scim (13.2 ml/s) for each transmitter and remote setpoint |
| Mounting | Upright on surface of wall or panel |
| Dimensions | 6-3/4 x 7-7/16 x 4" (172 x 189 x 102 mm) |