This temperature transmitter is configured for RTD Sensor, -58 to 392°F (-50 to 200°C), Class B Accuracy. It has range of -58.0 to 392.0°F (-50.0 to 200.0°C). It suits thermowell temperature measurement and hvac temperature monitoring.
This temperature transmitter is configured for RTD Sensor, -58 to 392°F (-50 to 200°C), Class B Accuracy. It has range of -58.0 to 392.0°F (-50.0 to 200.0°C). It suits thermowell temperature measurement and hvac temperature monitoring.
The PRTXD Series are 2-wire transmitters that provide a 4 to 20 mA signal representing temperature. The units include a 4½ digit display and the RTD sensor.
The NEMA 4X (IP66) housing protects the electronics. Units are available with spring-loaded probes for use with thermowells.
Features
Applications
| Series | PRTXD Series |
| Type | temperature transmitter |
| Input | RTD Sensor |
| Range | -58 to 392°F (-58 to 392°F (-50 to 200°C)) |
| Configuration | Class B Accuracy |
| Configuration | 0.1 Resolution |
| Configuration | 4" (10.2 cm) |
| Configuration | 1/2" (12.7 mm) NPT Male Thread |
| Input | 100 Ω RTD |
| Supply voltage | 8 V DC to 32 V DC |
| Sensor | 100 Ω RTD element, 0.00385 alpha coefficient IEC-751 class B: ±0.3°C at 0°C, ±1.1°C at 302°F (150°C) |
| Display | 4 1/2 digit LCD, 1/2" (12.7 mm) digit height, 4 readings per second, nominal display update rate |
| Range | -58.0 to 392.0°F (-50.0 to 200.0°C) |
| Resolution | 0.1 degree |
| Accuracy | ±0.1% of span plus maximum sensor error of ±0.3°C at 0°C or ±1.1°C at 302°F (150°C) |
| Output | 4 to 20 mA |
| Typical Loop Supply Voltage | Any DC supply/loop resistance that maintains 8 to 32 V DC at gauge terminals (reverse polarity protected) |
| Material and Color | NEMA 4X (IP66) ABS/Polycarbonate housing, light gray gasketed rear cover |
| Probe Material | 1/2 NPT male hex nipple, 316 stainless steel probe sheath |
| Operating Temperature (Electronics) | -4 to 185°F (-20 to 85°C) |
| Storage Temperature | -40 to 203°F (-40 to 95°C) |
| Wiring Connections | 3' (0.9 m) long, 2-conductor 22 AWG cable |
| Output / Loop Output Characteristics | 4 to 20 mA output (see chart for loop voltage characteristics), minimum 8 V required at gauge terminals at all times for proper operation |
| Out of Range Indication | ALARM 1: On display above 392°F (200°C); ALARM 2: On display below -58°F (-50°C) |
| Test Function | Front panel TEST button when held, sets loop current and display to test calibration level, independent of temperature input to allow testing of system operation |
| Connection and Probe Material | 1/2 NPT male hex nipple, 316 stainless steel probe sheath |
| Weight (Transmitter) | Approx12 oz (340 g) |
| Shipping Weight | Approx1 lb (450 g) |
| Series | PRTXD Series |
| Type | temperature transmitter |
| Input | RTD Sensor |
| Range | -58 to 392°F (-58 to 392°F (-50 to 200°C)) |
| Configuration | Class B Accuracy |
| Configuration | 0.1 Resolution |
| Configuration | 4" (10.2 cm) |
| Configuration | 1/2" (12.7 mm) NPT Male Thread |
| Input | 100 Ω RTD |
| Supply voltage | 8 V DC to 32 V DC |
| Sensor | 100 Ω RTD element, 0.00385 alpha coefficient IEC-751 class B: ±0.3°C at 0°C, ±1.1°C at 302°F (150°C) |
| Display | 4 1/2 digit LCD, 1/2" (12.7 mm) digit height, 4 readings per second, nominal display update rate |
| Range | -58.0 to 392.0°F (-50.0 to 200.0°C) |
| Resolution | 0.1 degree |
| Accuracy | ±0.1% of span plus maximum sensor error of ±0.3°C at 0°C or ±1.1°C at 302°F (150°C) |
| Output | 4 to 20 mA |
| Typical Loop Supply Voltage | Any DC supply/loop resistance that maintains 8 to 32 V DC at gauge terminals (reverse polarity protected) |
| Material and Color | NEMA 4X (IP66) ABS/Polycarbonate housing, light gray gasketed rear cover |
| Probe Material | 1/2 NPT male hex nipple, 316 stainless steel probe sheath |
| Operating Temperature (Electronics) | -4 to 185°F (-20 to 85°C) |
| Storage Temperature | -40 to 203°F (-40 to 95°C) |
| Wiring Connections | 3' (0.9 m) long, 2-conductor 22 AWG cable |
| Output / Loop Output Characteristics | 4 to 20 mA output (see chart for loop voltage characteristics), minimum 8 V required at gauge terminals at all times for proper operation |
| Out of Range Indication | ALARM 1: On display above 392°F (200°C); ALARM 2: On display below -58°F (-50°C) |
| Test Function | Front panel TEST button when held, sets loop current and display to test calibration level, independent of temperature input to allow testing of system operation |
| Connection and Probe Material | 1/2 NPT male hex nipple, 316 stainless steel probe sheath |
| Weight (Transmitter) | Approx12 oz (340 g) |
| Shipping Weight | Approx1 lb (450 g) |