Image is for reference only, refer to product info for complete details.
Designed for closed-loop PID control, this 1/8 DIN controller accepts thermocouple, RTD, thermistor, analog, and strain-gauge inputs and provides relay and analog outputs. It runs on a DC supply, shows readings on a dual 4-digit display, and connects via USB and EtherNet/IP. Great for oven, furnace, and process temperature regulation.
Designed for closed-loop PID control, this 1/8 DIN controller accepts thermocouple, RTD, thermistor, analog, and strain-gauge inputs and provides relay and analog outputs. It runs on a DC supply, shows readings on a dual 4-digit display, and connects via USB and EtherNet/IP. Great for oven, furnace, and process temperature regulation.
The PLATINUM Series family of microprocessor-based PID controllers offer unparalleled flexibility in process measurement. While extremely powerful and versatile, great care has gone into designing a product that is very easy to set-up and use.
The automatic hardware configuration recognition eliminates the need for jumpers and allows the firmware to automatically simplify itself, eliminating all menu options that do not apply to a specific configuration. Offered in 1/32, 1/16, and 1/8 DIN sizes, the 1/16 and 1/8 DIN models can be configured with dual displays. Models are available with single and dual 4 digit displays or single 6 digit display.
The voltage or current inputs are bipolar and fully scalable to virtually all engineering units, with a selectable decimal point that is perfect for use with pressure, flow, or other process input.
Control can be achieved by using the on/off or PID heat/cool control strategy. PID control can be optimized with an auto-tune feature; and in addition, a fuzzy logic adaptive tuning mode allows the PID algorithm to be continuously optimized.
The instrument offers up to 16 ramp and soak segments per ramp and soak program, with auxiliary event actions available with each segment. Up to 99 saved programs which can be chained to create up to 1584 discreet segments. Multiple alarms can be configured for above, below, hi/lo, and band triggering using either absolute or deviation alarm trigger points.
The PLATINUM Series device features a large, three-color, programmable display with the capability to change color and/or change the state of designated outputs every time an Alarm is triggered. Various configurations of mechanical relay, SSR, dc pulse, and analog voltage or current outputs are available. Up to 6 programmable outputs, including isolated and non-isolated, are best in class.
Every unit comes standard with USB communications for firmware updates, configuration management, and data transfer. The Analog Output is fully scalable and may be configured as a proportional controller or as retransmission to follow your display.
The remote setpoint feature of the PLATINUM Series Controllers can be used in a variety of applications where setpoints can be sent to the controllers from remote devices such as manual pots, transmitters, computers, etc. This feature can also be used to set-up a "cascade control" system, where the remote setpoint input is generated by another controller.
Cascade control schemes can provide tighter control of a process when you have two linked variables, one of which has a much slower (typically 4X or more) response than the other. The slower responding variable is used as the input to the primary or master controller, and the faster responding variable is used as the input to the secondary or slave controller. The output of the primary controller is scaled to be used as the setpoint for the secondary controller.
Additional features usually found only on more expensive controllers make this the most powerful product in its class.
Optional "embedded ethernet" on the 1/16 and 1/8 DIN models allow the units to connect directly to an Ethernet network and transmit data in standard TCP/IP packets, or serve Web pages over a LAN or the Internet. Optional serial communications are also available configurable as RS232 or RS485, with straightforward ASCII commands or MODBUS(R). All three types of communications interfaces (USB, Ethernet, and Serial) can be installed and active simultaneously.
Features
Applications
| Input types | Thermocouple, RTD, thermistor, analog voltage, analog current, strain |
| Current input | 4 to 20 mA, 0 to 24 mA scalable |
| Voltage input | -100 to 100 mV, -1 to 1 V, -10 to 10 Vdc scalable |
| Thermocouple input (ITS 90) | K, J, T, E, R, S, B, C, N |
| RTD input (ITS 90) | 100/500/1000 Ohm Pt sensor, 2-, 3- or 4-wire; 0.00385, 0.00392 (100 Ohm only), or 0.003916 (100 Ohm only) curves |
| Thermistor input | 2252 Ohm, 5K Ohm, 10K Ohm |
| Strain input | ±50 mV, ±100 mV |
| Configuration | Differential |
| Polarity | Bipolar |
| Resolution | 0.1° temperature; 10 µV process |
| Input impedances | Process/strain: 10M Ohm for ±100 mV, 1M Ohm for other voltage ranges; process current: 5 Ohm; thermocouple: 10K Ohm max |
| Auxiliary input (remote setpoint) | 3.5K Ohm for 0 to 10 V, 50K Ohm for 0 to 1 V, 50 Ohm for current |
| Temperature stability | RTD: 0.04°C/°C; thermocouple @ 25°C (77°F): 0.05°C/°C (cold junction compensation); process/strain: 50 ppm/°C |
| A/D conversion | 24-bit sigma delta |
| Reading rate | 20 samples per second |
| Digital filter | Programmable from 0.05 seconds (filter = 1) to 6.4 seconds (filter = 128) |
| CMRR | 120 dB |
| Excitation | Firmware selectable (no jumpers to set) to 5, 10, 12, and 24 Vdc @ 25 mA |
| Setpoint adjustment | 4 digit (-9999 to +9999 counts), 6 digit (-99999 to +999999 counts) |
| Warm-up to rated accuracy | 30 minutes |
| Action | Reverse (heat), direct (cool), or heat/cool |
| Auto-tune | Operator initiated from front panel |
| Adaptive tune | User selectable; fuzzy logic continuous PID tuning optimization |
| Control modes | ON/OFF or the following time/amplitude proportional control modes; selectable manual or auto PID, proportional, proportional with integral, proportional with derivative |
| Cycle time | 0.1 to 199 seconds |
| Ramp and soak | Up to 99 saved ramp and soak programs, up to 8 ramp and 8 soak segments with individually selectable events per program, chainable |
| Ramp and soak segment times | 00.00 to 99.59 (HH:MM) or 00.00 to 99.59 (MM:SS) |
| Analog output | Non-isolated, programmable for control or retransmission; voltage output 0 to 10 V output, 500 Ohm min, accuracy 0.1%; current output 0 to 20 mA output, 500 Ohm max, accuracy 0.1%; step response time 100 ms |
| DC Pulse output | Non-isolated; 10 Vdc at 20 mA |
| SPST Relay output | Single pole, single throw mechanical relay, 250 Vac or 30 Vdc at 3 A (resistive load) |
| SPDT Relay output | Single pole, double throw mechanical relay, 250 Vac or 30 Vdc at 3 A (resistive load) |
| SSR output | 20 to 265 Vac at 0.05 to 0.5 A (resistive load); continuous |
| Isolated DC Pulse output | 1.5 kV isolation; 10 Vdc at 20 mA |
| Isolated analog output | 1.5 kV isolation, programmable for control or retransmission; voltage output 0 to 10 V output, 500 Ohm min, accuracy 0.1%; current output 0 to 20 mA output, 500 Ohm max, accuracy 0.1%; step response time 100 ms |
| USB connection | Female micro-USB |
| Ethernet connection | Standard RJ45 |
| Serial connection | Screw terminals |
| USB | USB 2.0 host or device |
| Ethernet standards compliance | IEEE 802.3 10/100 Base-T auto-switching, TCP/IP, ARP, HTTPGET |
| Serial | Software selectable RS232 or RS485; programmable 1200 to 115.2 K baud |
| Protocols | OMEGA ASCII, MODBUS ASCII/RTU |
| Approvals | UL, cUL, CE, UKCA |
| Power to input/output isolation | 2300 Vac per 1 min test; 1500 Vac per 1 min test (low voltage/power option) |
| Power to relays/SSR outputs isolation | 2300 Vac per 1 min test |
| Relays/SSR to relay/SSR outputs isolation | 2300 Vac per 1 min test |
| RS232/RS485 to inputs/outputs isolation | 500 Vac per 1 min test |
| Display | 4-digit, 9-segment LED |
| Environmental conditions | 0 to 50°C (32 to 122°F), 90% RH non-condensing |
| External fuse required | Time-delay, UL 248-14 Listed: 100 mA/250 V; 400 mA/250 V (low voltage option); time-lag, IEC 127-3 Recognized: 100 mA/250 V; 400 mA/250 V (low voltage option) |
| Line voltage/power | 90 to 240 Vac ±10%, 50 to 400 Hz, 110 to 375 Vdc, equivalent voltage |
| Process/strain range and accuracy | Process voltage ±50 mV, ±100 mV, ±1, ±10 Vdc: 0.03% FS; process current scalable within 0 to 24 mA: 0.03% FS |
| Iron-Constantan range and accuracy | -210 to 1200°C (-346 to 2192°F): 0.4°C (0.7°F) |
| CHROMEGA-ALOMEGA range and accuracy | -270 to -160°C (-454 to -256°F): 1.0°C (1.8°F); -160 to 1372°C (-256 to 2502°F): 0.4°C (0.7°F) |
| Copper-Constantan range and accuracy | -270 to -190°C (-454 to -310°F): 1.0°C (1.8°F); -190 to 400°C (-310 to 752°F): 0.4°C (0.7°F) |
| CHROMEGA-Constantan range and accuracy | -270 to -220°C (-454 to -364°F): 1.0°C (1.8°F); -220 to 1000°C (-364 to 1832°F): 0.4°C (0.7°F) |
| Pt/13%Rh-Pt range and accuracy | -50 to 40°C (-58 to 104°F): 1.0°C (1.8°F); 40 to 1788°C (104 to 3250°F): 0.5°C (0.9°F) |
| Pt/10%Rh-Pt range and accuracy | -50 to 100°C (-58 to 212°F): 1.0°C (1.8°F); 100 to 1768°C (212 to 3214°F): 0.5°C (0.9°F) |
| 30%Rh-Pt/6%Rh-Pt range and accuracy | 100 to 640°C (212 to 1184°F): 1.0°C (1.8°F); 640 to 1820°C (1184 to 3308°F): 0.5°C (0.9°F) |
| 5%Re-W/26%Re-W range and accuracy | 0 to 2320°C (32 to 4208°F): 0.4°C (0.7°F) |
| Nicrosil-Nisil range and accuracy | -250 to -100°C (-418 to -148°F): 1.0°C (1.8°F); -100 to 1300°C (-148 to 2372°F): 0.4°C (0.7°F) |
| Pt, 0.00385, 100 Ohm, 500 Ohm, 1000 Ohm range and accuracy | -200 to 850°C (-328 to 1562°F): 0.3°C (0.7°F) |
| Pt, 0.003916, 100 Ohm range and accuracy | -200 to 660°C (-328 to 1220°F): 0.3°C (0.7°F) |
| Pt, 0.00392, 100 Ohm range and accuracy | -200 to 660°C (-328 to 1220°F): 0.3°C (0.7°F) |
| Thermistor 2252 Ohm range and accuracy | -40 to 120°C (-40 to 248°F): 0.2°C (0.35°F) |
| Thermistor 5K Ohm range and accuracy | -30 to 140°C (-22 to 284°F): 0.2°C (0.35°F) |
| Thermistor 10K Ohm range and accuracy | -20 to 150°C (-4 to 302°F): 0.2°C (0.35°F) |
| Size/cutout | 1/8 DIN |
| Output 1 | SPDT Relay |
| Output 2 | Analog |
| Display digit height | 21 mm (0.83") and 10.2 mm (0.40") |
| Protection | NEMA 1 front bezel |
| Low voltage/power option | 20 to 36 Vdc, 4 W power |
| -006 | Isolated analog output |
| -EIP | Ethernet with embedded web server |
| Dimensions | 48 H x 96 W x 127 mm D (1.89 x 3.78 x 5") Panel cutout: 45 H x 92 mm W (1.772 x 3.622"), 1/8 DIN |
| Input types | Thermocouple, RTD, thermistor, analog voltage, analog current, strain |
| Current input | 4 to 20 mA, 0 to 24 mA scalable |
| Voltage input | -100 to 100 mV, -1 to 1 V, -10 to 10 Vdc scalable |
| Thermocouple input (ITS 90) | K, J, T, E, R, S, B, C, N |
| RTD input (ITS 90) | 100/500/1000 Ohm Pt sensor, 2-, 3- or 4-wire; 0.00385, 0.00392 (100 Ohm only), or 0.003916 (100 Ohm only) curves |
| Thermistor input | 2252 Ohm, 5K Ohm, 10K Ohm |
| Strain input | ±50 mV, ±100 mV |
| Configuration | Differential |
| Polarity | Bipolar |
| Resolution | 0.1° temperature; 10 µV process |
| Input impedances | Process/strain: 10M Ohm for ±100 mV, 1M Ohm for other voltage ranges; process current: 5 Ohm; thermocouple: 10K Ohm max |
| Auxiliary input (remote setpoint) | 3.5K Ohm for 0 to 10 V, 50K Ohm for 0 to 1 V, 50 Ohm for current |
| Temperature stability | RTD: 0.04°C/°C; thermocouple @ 25°C (77°F): 0.05°C/°C (cold junction compensation); process/strain: 50 ppm/°C |
| A/D conversion | 24-bit sigma delta |
| Reading rate | 20 samples per second |
| Digital filter | Programmable from 0.05 seconds (filter = 1) to 6.4 seconds (filter = 128) |
| CMRR | 120 dB |
| Excitation | Firmware selectable (no jumpers to set) to 5, 10, 12, and 24 Vdc @ 25 mA |
| Setpoint adjustment | 4 digit (-9999 to +9999 counts), 6 digit (-99999 to +999999 counts) |
| Warm-up to rated accuracy | 30 minutes |
| Action | Reverse (heat), direct (cool), or heat/cool |
| Auto-tune | Operator initiated from front panel |
| Adaptive tune | User selectable; fuzzy logic continuous PID tuning optimization |
| Control modes | ON/OFF or the following time/amplitude proportional control modes; selectable manual or auto PID, proportional, proportional with integral, proportional with derivative |
| Cycle time | 0.1 to 199 seconds |
| Ramp and soak | Up to 99 saved ramp and soak programs, up to 8 ramp and 8 soak segments with individually selectable events per program, chainable |
| Ramp and soak segment times | 00.00 to 99.59 (HH:MM) or 00.00 to 99.59 (MM:SS) |
| Analog output | Non-isolated, programmable for control or retransmission; voltage output 0 to 10 V output, 500 Ohm min, accuracy 0.1%; current output 0 to 20 mA output, 500 Ohm max, accuracy 0.1%; step response time 100 ms |
| DC Pulse output | Non-isolated; 10 Vdc at 20 mA |
| SPST Relay output | Single pole, single throw mechanical relay, 250 Vac or 30 Vdc at 3 A (resistive load) |
| SPDT Relay output | Single pole, double throw mechanical relay, 250 Vac or 30 Vdc at 3 A (resistive load) |
| SSR output | 20 to 265 Vac at 0.05 to 0.5 A (resistive load); continuous |
| Isolated DC Pulse output | 1.5 kV isolation; 10 Vdc at 20 mA |
| Isolated analog output | 1.5 kV isolation, programmable for control or retransmission; voltage output 0 to 10 V output, 500 Ohm min, accuracy 0.1%; current output 0 to 20 mA output, 500 Ohm max, accuracy 0.1%; step response time 100 ms |
| USB connection | Female micro-USB |
| Ethernet connection | Standard RJ45 |
| Serial connection | Screw terminals |
| USB | USB 2.0 host or device |
| Ethernet standards compliance | IEEE 802.3 10/100 Base-T auto-switching, TCP/IP, ARP, HTTPGET |
| Serial | Software selectable RS232 or RS485; programmable 1200 to 115.2 K baud |
| Protocols | OMEGA ASCII, MODBUS ASCII/RTU |
| Approvals | UL, cUL, CE, UKCA |
| Power to input/output isolation | 2300 Vac per 1 min test; 1500 Vac per 1 min test (low voltage/power option) |
| Power to relays/SSR outputs isolation | 2300 Vac per 1 min test |
| Relays/SSR to relay/SSR outputs isolation | 2300 Vac per 1 min test |
| RS232/RS485 to inputs/outputs isolation | 500 Vac per 1 min test |
| Display | 4-digit, 9-segment LED |
| Environmental conditions | 0 to 50°C (32 to 122°F), 90% RH non-condensing |
| External fuse required | Time-delay, UL 248-14 Listed: 100 mA/250 V; 400 mA/250 V (low voltage option); time-lag, IEC 127-3 Recognized: 100 mA/250 V; 400 mA/250 V (low voltage option) |
| Line voltage/power | 90 to 240 Vac ±10%, 50 to 400 Hz, 110 to 375 Vdc, equivalent voltage |
| Process/strain range and accuracy | Process voltage ±50 mV, ±100 mV, ±1, ±10 Vdc: 0.03% FS; process current scalable within 0 to 24 mA: 0.03% FS |
| Iron-Constantan range and accuracy | -210 to 1200°C (-346 to 2192°F): 0.4°C (0.7°F) |
| CHROMEGA-ALOMEGA range and accuracy | -270 to -160°C (-454 to -256°F): 1.0°C (1.8°F); -160 to 1372°C (-256 to 2502°F): 0.4°C (0.7°F) |
| Copper-Constantan range and accuracy | -270 to -190°C (-454 to -310°F): 1.0°C (1.8°F); -190 to 400°C (-310 to 752°F): 0.4°C (0.7°F) |
| CHROMEGA-Constantan range and accuracy | -270 to -220°C (-454 to -364°F): 1.0°C (1.8°F); -220 to 1000°C (-364 to 1832°F): 0.4°C (0.7°F) |
| Pt/13%Rh-Pt range and accuracy | -50 to 40°C (-58 to 104°F): 1.0°C (1.8°F); 40 to 1788°C (104 to 3250°F): 0.5°C (0.9°F) |
| Pt/10%Rh-Pt range and accuracy | -50 to 100°C (-58 to 212°F): 1.0°C (1.8°F); 100 to 1768°C (212 to 3214°F): 0.5°C (0.9°F) |
| 30%Rh-Pt/6%Rh-Pt range and accuracy | 100 to 640°C (212 to 1184°F): 1.0°C (1.8°F); 640 to 1820°C (1184 to 3308°F): 0.5°C (0.9°F) |
| 5%Re-W/26%Re-W range and accuracy | 0 to 2320°C (32 to 4208°F): 0.4°C (0.7°F) |
| Nicrosil-Nisil range and accuracy | -250 to -100°C (-418 to -148°F): 1.0°C (1.8°F); -100 to 1300°C (-148 to 2372°F): 0.4°C (0.7°F) |
| Pt, 0.00385, 100 Ohm, 500 Ohm, 1000 Ohm range and accuracy | -200 to 850°C (-328 to 1562°F): 0.3°C (0.7°F) |
| Pt, 0.003916, 100 Ohm range and accuracy | -200 to 660°C (-328 to 1220°F): 0.3°C (0.7°F) |
| Pt, 0.00392, 100 Ohm range and accuracy | -200 to 660°C (-328 to 1220°F): 0.3°C (0.7°F) |
| Thermistor 2252 Ohm range and accuracy | -40 to 120°C (-40 to 248°F): 0.2°C (0.35°F) |
| Thermistor 5K Ohm range and accuracy | -30 to 140°C (-22 to 284°F): 0.2°C (0.35°F) |
| Thermistor 10K Ohm range and accuracy | -20 to 150°C (-4 to 302°F): 0.2°C (0.35°F) |
| Size/cutout | 1/8 DIN |
| Output 1 | SPDT Relay |
| Output 2 | Analog |
| Display digit height | 21 mm (0.83") and 10.2 mm (0.40") |
| Protection | NEMA 1 front bezel |
| Low voltage/power option | 20 to 36 Vdc, 4 W power |
| -006 | Isolated analog output |
| -EIP | Ethernet with embedded web server |
| Dimensions | 48 H x 96 W x 127 mm D (1.89 x 3.78 x 5") Panel cutout: 45 H x 92 mm W (1.772 x 3.622"), 1/8 DIN |