Converts a current input signal to a linearly proportional pneumatic output pressure. Features a 4-20 mA input and 3-15 psi (20-100 kPA) output.
Converts a current input signal to a linearly proportional pneumatic output pressure. Features a 4-20 mA input and 3-15 psi (20-100 kPA) output.
The rugged NEMA 4X enclosure allows splashdown and outdoor installation.
Features
Applications
| Service | Oil free, clean dry air filtered to 40 microns |
| Input Signal | 4-20 mA |
| Input Impedance | IP-42: 180 ohms; IP-43 and IP-44: 220 ohms |
| Air Pressure | Minimum: 3 psig (21 kPa) above maximum output Maximum: 100 psig (700 kPa) |
| Linearity | <±0.75% of span |
| Hysteresis | <1% of span |
| Repeatability | <0.5% of span |
| Supply Pressure Sensitivity | <±0.1% of span per psig (<±0.15% of span per 10 kPa) |
| Power Requirements | Loop powered |
| Temperature Limits | -20 to 140°F (-30 to 60°C) |
| Pressure Connections | 1/4" female NPT |
| Electrical Connection | 1/2" female NPT |
| Air Consumption | 0.03 SCFM (0.5 m3/h) typical |
| Output Capacity | 4.5 SCFM (7.6 m3/h ANR) at 25 psig (175 kPa) supply 12 SCFM (20 m3/h) at 100 psig (700 kPa) supply |
| Relief Capacity | 2 SCFM (3.4 m3/h) at 5 psig (35 kPa) above 20 psig (140 kPa) setpoint |
| Weight | 2.1 lb (0.94 kg) |
| Agency Approvals | CE, FM |
| Service | Oil free, clean dry air filtered to 40 microns |
| Input Signal | 4-20 mA |
| Input Impedance | IP-42: 180 ohms; IP-43 and IP-44: 220 ohms |
| Air Pressure | Minimum: 3 psig (21 kPa) above maximum output Maximum: 100 psig (700 kPa) |
| Linearity | <±0.75% of span |
| Hysteresis | <1% of span |
| Repeatability | <0.5% of span |
| Supply Pressure Sensitivity | <±0.1% of span per psig (<±0.15% of span per 10 kPa) |
| Power Requirements | Loop powered |
| Temperature Limits | -20 to 140°F (-30 to 60°C) |
| Pressure Connections | 1/4" female NPT |
| Electrical Connection | 1/2" female NPT |
| Air Consumption | 0.03 SCFM (0.5 m3/h) typical |
| Output Capacity | 4.5 SCFM (7.6 m3/h ANR) at 25 psig (175 kPa) supply 12 SCFM (20 m3/h) at 100 psig (700 kPa) supply |
| Relief Capacity | 2 SCFM (3.4 m3/h) at 5 psig (35 kPa) above 20 psig (140 kPa) setpoint |
| Weight | 2.1 lb (0.94 kg) |
| Agency Approvals | CE, FM |