UL listed for use in Class I, Groups A, B, C, & D; Class II, Groups E, F, & G and Class III atmospheres, Directive 94/9/EC (ATEX) Compliant for CE ATEX II 2G Exd IIB+H2 T6, CSA & FM approved for Class I, Div. 1, Groups B, C, D; Class II, Div. 1, Groups E, F, G and Class III atmospheres IECEx Ex d IIB+H2 T6 (-40°C < Ta < 60°C).
Measures positive, negative, or differential pressure of air and natural gases in ranges from 1 "w.c. (0.249 kPa) to 150 psid (10.34 bar). The dual push pads on the front panel control the on/off, auto-zero, and pressure unit selection, allowing for simple operation with no set up needed.
Convert pressure into a standard 4-20 mA output signal. It can be used to accurately measure compatible gases and liquids compatible with its 316SS/316LSS wetted parts. Series IS626 full scale accuracy is 0.25%. Designed for industrial environments with a NEMA 4X (IP66) housing, this transmitter resists most effects of shock and vibration.
Provides a 4 to 20 mA process output, a robust NEMA 4X enclosure, plus a large LCD display that can be programmed to read in pressure, velocity or flow. Features security level, English or Metric engineering units, pressure, velocity or flow operation, K-factor, volumetric flow operation, plus many more.
A microprocessor-based high performance transmitter, which has flexible pressure calibration, push button configuration, and programmable using HART® Communication. The Series 3200G is capable of being configured with the zero and span buttons, a field calibrator is not required for configuration.
Approved for use in hazardous location applications. Intrinsically safe for Class I, II, & I, Div. 1, Groups A, B, C, D, E, F & G; Class I, Zone 0 Aex ia IIC.